ISO/IEC 14763-3:2014

There has been a number of changes in the test limits between ISO/IEC 14763-3:2006 and ISO/IEC 14763-3:2014 for the 1 Jumper Reference.

Please ensure your CertiFiber Pro and OptiFiber Pro have the latest software.
 

ISO/IEC 14763-3:2006 (In our certification products, this is labelled ISO/IEC 14763-3)

  • for MMF: Limit = 0.6 dB + Σ (cable attenuation) + Σ (embedded connection attenuation)
  • for SMF: Limit = 1.0 dB + Σ (cable attenuation) + Σ (embedded connection attenuation)


ISO/IEC 14763-3:2014

  • for MMF: Limit = 1.0 dB + Σ (cable attenuation) + Σ (embedded connection attenuation)
  • for SMF: Limit = 1.3 dB + Σ (cable attenuation) + Σ (embedded connection attenuation)

     

ISO/IEC 14763-3:2014 Corrigendum March 2015  (In our certification products, this is labelled ISO/IEC 14763-3:2014)

  • for MMF: Limit = 1.0 dB + Σ (cable attenuation) + Σ (embedded connection attenuation)
  • for SMF: Limit = 1.5 dB + Σ (cable attenuation) + Σ (embedded connection attenuation)

 

Please check with your cabling vendor or consultant as to which limit you should be using